首页> 外文期刊>Modern Applied Science >FEM Application for Evaluating and Improving the Insulation System of the 33kV Wound-Core Type Distribution Transformer
【24h】

FEM Application for Evaluating and Improving the Insulation System of the 33kV Wound-Core Type Distribution Transformer

机译:FEM在评估和改进33kV绕芯式配电变压器绝缘系统中的应用

获取原文
           

摘要

This paper presents a 2-D and 3-D FE model of 250kVA, 33/0.416 kV wound core type distribution transformer, simulated using ANSYS 17.2 software in order to evaluate the insulation system via dielectric strength under power frequency and induced withstand tests and using two types of analysis, time-harmonic analysis to simulate the dielectric tests, and electro-static analysis to calculate the capacitance matrix. The assessment is based on the maximum allowable electric field intensity. the obtained results were compared with those of the real test, and the values of electric stress were less than the maximum allowable values. also, improvements to the presented model were applied following the transformer assessment. The improvement to the transformer insulation structure was done using three suggested finite element models included reduction and changing the materials type. the results were reviewed in form of contour plots, vector plots, and curves.
机译:本文介绍了使用ANSYS 17.2软件模拟的250kVA,33 / 0.416 kV绕线型配电变压器的2-D和3-D FE模型,以便通过工频下的介电强度评估绝缘系统,并通过耐压测试和两种类型的分析:时谐分析以模拟介电测试,静电分析以计算电容矩阵。评估基于最大允许电场强度。将得到的结果与真实测试的结果进行比较,电应力的值小于最大允许值。同样,在评估变压器后,对提出的模型进行了改进。使用三个建议的有限元模型对变压器绝缘结构进行了改进,包括减少和改变材料类型。结果以等高线图,矢量图和曲线的形式进行了审查。