首页> 外文期刊>Materials >Experimental Study on the Fire Performance of Tubular Steel Columns with Membrane Protections for Prefabricated and Modular Steel Construction
【24h】

Experimental Study on the Fire Performance of Tubular Steel Columns with Membrane Protections for Prefabricated and Modular Steel Construction

机译:预制和模块化钢结构膜保护钢管柱耐火性能试验研究。

获取原文
       

摘要

Experimental research was conducted to study the fire resistance of steel tubular columns used in prefabricated and modular construction. In order to achieve high-efficient prefabrication and fast on-site installation, membrane protections using board products and thermal insulation blankets are adopted as the favorable protection method. Three protected tubular columns were tested in a full-scale column furnace with axial load applied. The study variables were different membranes, including fiber reinforced calcium silicate (FRCS) boards, rock wool and aluminum silica (Fiberfrax) insulations. The results suggest that one layer of 12 mm FRCS board with rock wool insulation has insufficient fire protection. However, steel columns protected with two layers of 12 mm FRCS boards with insulation appeared to have good fire resistances and could achieve a fire resistance rating as high as 2.5~3.0 h.
机译:进行了实验研究,以研究预制和模块化结构中使用的钢管柱的耐火性。为了实现高效的预制和快速的现场安装,采用木板产品和隔热毯进行薄膜保护是一种有利的保护方法。在施加轴向载荷的全尺寸柱式炉中测试了三个受保护的管状柱。研究变量是不同的膜,包括纤维增强硅酸钙(FRCS)板,岩棉和硅铝(Fiberfrax)隔热材料。结果表明,一层12 mm的FRCS绝缘岩棉板防火性能不足。但是,用两层绝缘的12 mm FRCS板保护的钢柱似乎具有良好的耐火性,并且可以达到高达2.5〜3.0 h的耐火等级。