首页> 外文期刊>Energies >Smart Meter Data-Based Three-Stage Algorithm to Calculate Power and Energy Losses in Low Voltage Distribution Networks ?
【24h】

Smart Meter Data-Based Three-Stage Algorithm to Calculate Power and Energy Losses in Low Voltage Distribution Networks ?

机译:基于智能电表数据的三阶段算法,计算低压配电网的功率和能量损耗

获取原文
           

摘要

In this paper, an improved smart meter data-based three-stage algorithm to calculate the power/energy losses in three-phase networks with the voltage level below 0.4 kV (low voltage—LV) is presented. In the first stage, the input data regarding the hourly active and reactive powers of the consumers and producers are introduced. The powers are loaded from the database of the smart metering system (SMS) for the consumers and producers integrated in this system or files containing the characteristic load profiles established by the Distribution Network Operator for the consumers, which have installed the conventional meters non-integrated in the SMS. In the second stage, a function, which is based on the work with the structure vectors, was implemented to easily identify the configuration of analysed networks. In the third stage, an improved version of a forward/backward sweep-based algorithm was proposed to quickly calculate the power/energy losses to three-phase LV distribution networks in a balanced and unbalanced regime. A real LV rural distribution network from a pilot zone belonging to a Distribution Network Operator from Romania was used to confirm the accuracy of the proposed algorithm. The comparison with the results obtained using the DigSilent PowerFactory Simulation Package certified the performance of the algorithm, with the mean absolute percentage error (MAPE) being 0.94%.
机译:本文提出了一种改进的基于智能电表数据的三阶段算法,该算法可计算电压等级低于0.4 kV(低压-LV)的三相网络的功率/能量损耗。在第一阶段,引入有关消费者和生产者的每小时有功功率和无功功率的输入数据。从集成在该系统中的消费者和生产者的智能电表系统(SMS)的数据库中加载功率,或者从配电网络运营商为消费者建立的文件中包含特征负荷曲线,这些文件已安装了非集成的常规电表在短信中。在第二阶段,实现了一个基于结构向量的功能的函数,可轻松识别被分析网络的配置。在第三阶段,提出了一种基于向前/向后扫描的算法的改进版本,可以在平衡和不平衡状态下快速计算三相低压配电网的功率/能量损耗。来自罗马尼亚的配电网运营商的试验区中的实际LV农村配电网用于确认该算法的准确性。与使用DigSilent PowerFactory仿真软件包获得的结果进行比较,证明了该算法的性能,平均绝对百分比误差(MAPE)为0.94%。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号