摘要

For the purpose of increasing quality, continuity and, at the same time, of increasing reliability and decreasing the losses in an electric power system (EPS), there is an emerging need for preventive diagnostic testing. From the standpoint of an electric power system availability, it is desirable to perform as many tests as possible without a violation of operating conditions of the system itself. The paper presents the thermographic testing of a HV disconnector, as an online testing with the aim of preventive maintenance and condition diagnosis of particular elements, as well as the suggestions for taking adequate measures with the aim of removing potential malfunctions.For the testing results to be quality and to give a reliable information, the load of a facility must be bigger that 50% of the nominal power. On the basis of obtained thermograms, the analysis of the disconnector and its contacts is performed, as well as of the contacts towards other elements in the facility.
机译:为了提高质量,连续性并同时提高可靠性并减少电力系统(EPS)中的损耗,对预防性诊断测试的需求不断增长。从电力系统可用性的观点出发,期望在不违反系统本身的工作条件的情况下进行尽可能多的测试。本文介绍了高压隔离开关的热成像测试,在线测试,旨在预防性维护和特定元件的状态诊断,并提出了采取适当措施以消除潜在故障的建议。为了保证质量并提供可靠的信息,设施的负载必须大于标称功率的50%。根据获得的热分析图,对隔离开关及其触点以及对设施中其他元件的触点进行分析。