首页> 外文期刊>Electrotehnica, Electronica, Automatica >Siguran?a ?n exploatare a stalpilor din beton armat aferente liniilor electrice – analize de cazSafety in use of reinforced concrete pillars of power lines – case analysesFull text in Romanian
【24h】

Siguran?a ?n exploatare a stalpilor din beton armat aferente liniilor electrice – analize de cazSafety in use of reinforced concrete pillars of power lines – case analysesFull text in Romanian

机译:电力线相关钢筋混凝土电线杆的操作安全-案例分析电力线钢筋混凝土支柱的使用安全-案例分析

获取原文
       

摘要

By visual observations the degradation of reinforced concrete pillars for the support of electricity distribution lines was analyzed. Following electrochemical and electrical measurements on the field, as well as some pH determinations and microbiological identification of mold species on degraded concrete samples, it was found that the advanced degradation state of the investigated pillars is due to the total de-alkalinization of the concrete (7 0.315VCu / CuSO4). Corrosion of steel bars and degradation of concrete was accelerated by polarization in A.C. (1.26Vrms between steel bars and ground, signal with high harmonic content - maximum value of 4.3Vpp being obtained at harmonic III). In the degradated concrete samples, the Trichoderma viride, Chaetomium globosum and Aspergillus niger species have been identified.
机译:通过视觉观察,分析了用于支撑配电线路的钢筋混凝土柱的退化。在现场进行电化学和电学测量以及某些pH值测定和降解的混凝土样品上霉菌种类的微生物鉴定后,发现所研究的柱子的高级降解状态是由于混凝土的总脱碱( 7 0.315VCu / CuSO4)。交流电中的极化作用加速了钢筋的腐蚀和混凝土的降解(钢筋与地面之间的电压为1.26Vrms,高谐波含量的信号-在谐波III处获得最大值4.3Vpp)。在降解的混凝土样品中,已鉴定出木霉,木毛龟和黑曲霉。