Heat Transfer Analysis of Two Phase Closed Thermosyphon using Aqueous Solution of n-Butanol

机译:正丁醇水溶液对两相闭式热虹吸管的传热分析

获取原文

摘要

Two phase closed thermosyphon is proved to be a good heat transfer device. A large amount of heat is transferred from evaporator section to condenser section with relatively a small temperature difference. In this paper, the heat transfer of two phase closed thermosyphon is analysed experimentally with different inclinations and heat input. For this experiment, two copper thermosyphons of length 1000 mm, inner diameter 17 mm and outer diameter 19 mm are designed. Both are charged with 60 ml of working fluid with an evaporator length of 400 mm and condenser length of 450 mm. One thermosyphon is charged with de-ionized water (DI) and the other with aqueous solution of n-butanol. It is found that the heat transfer coefficient of aqueous solution of n-butanol is higher than that of de-ionized water.