首页> 外文期刊>AIP Advances >Transformer sound level caused by core magnetostriction and winding stress displacement variation
【24h】

Transformer sound level caused by core magnetostriction and winding stress displacement variation

机译:铁心磁致伸缩和绕组应力位移变化引起的变压器声级

获取原文
           

摘要

Magnetostriction caused by the exciting variation of the magnetic core and the current conducted by the winding wired to the core has a significant result impact on a power transformer. This paper presents the sound of a factory transformer before on-site delivery for no-load tests. This paper also discusses the winding characteristics from the transformer full-load tests. The simulation and the measurement for several transformers with capacities ranging from 15 to 60 MVA and high voltage 132kV to low voltage 33 kV are performed. This study compares the sound levels for transformers by no-load test (core/magnetostriction) and full-load test (winding/displacement ε ). The difference between the simulated and the measured sound levels is about 3dB. The results show that the sound level depends on several parameters, including winding displacement, capacity, mass of the core and windings. Comparative results of magnetic induction of cores and the electromagnetic force of windings for no-load and full-load conditions are examined.
机译:由磁芯的励磁变化引起的磁致伸缩以及连接到磁芯的绕组所传导的电流会严重影响电源变压器。本文介绍了工厂变压器在现场交付进行空载测试之前的声音。本文还讨论了变压器满载测试中的绕组特性。对容量在15至60 MVA且高压132kV至低压33 kV的几台变压器进行了仿真和测量。这项研究通过空载测试(铁芯/磁致伸缩)和满载测试(绕组/位移ε)比较了变压器的声级。模拟声级与测量声级之间的差异约为3dB。结果表明,声级取决于几个参数,包括绕组的位移,容量,铁芯和绕组的质量。研究了在空载和满载条件下铁芯磁感应强度和绕组电磁力的比较结果。