首页> 外文期刊>British Journal of Applied Science and Technology >Fault Ride Through in Grid-connected WECSUsing FACTS
【24h】

Fault Ride Through in Grid-connected WECSUsing FACTS

机译:并网WECSUsing FACTS中的故障穿越

获取原文
           

摘要

This paper discusses the effectiveness of installing two types of FACTS devices, namely STATCOM and DVR to enhance the fault ride through (FRT) capability of a doubly fed induction generator (DFIG) applied in wind energy conversion systems (WECS). The response of the DFIG to a 3-phase ground fault is investigated with each of these devices. Comparing the stator and rotor voltages, stator and rotor currents, active and reactive power, of the two investigated systems is presented. PI controllers are employed to allow the rotor speed to follow the turbine speed and to adjust the applied rotor voltage magnitude and phase angle according to the wind turbine speed for maximum power tracking. This is achieved by controlling the two PWM converters connected between the rotor circuit and the electrical grid. Results showed a better FRT when using the STATCOM device with the DFIG.
机译:本文讨论了安装两种类型的FACTS设备(STATCOM和DVR)的有效性,以增强风能转换系统(WECS)中应用的双馈感应发电机(DFIG)的故障穿越能力(FRT)。这些设备中的每一个都研究了DFIG对三相接地故障的响应。比较了两个研究系统的定子和转子电压,定子和转子电流,有功和无功功率。 PI控制器用于允许转子速度跟随涡轮速度,并根据风力涡轮速度调整施加的转子电压幅度和相角,以实现最大功率跟踪。这是通过控制连接在转子电路和电网之间的两个PWM转换器来实现的。当将STATCOM设备与DFIG一起使用时,结果显示出更好的FRT。