High resistance grounding of 600 V power distribution systems is applied in hospitals, data centres and telecom facilities where supply availability is demanded. High resistance grounding provides service continuity during a ground fault. It also enhances electrical safety by preventing a ground fault from escalating into an arc flash incident. However, care must be taken during electrical system design to ensure that transient voltage surge suppressor (TVSS) and uninterruptible power supply (UPS) systems are properly applied. Installation of a TVSS or UPS designed for a solidly grounded system into a high resistance grounded (HRG) system can lead to unintended failures that reduce service continuity.
机译:600 V配电系统的高电阻接地适用于需要供电的医院,数据中心和电信设施。高电阻接地可在接地故障期间提供服务连续性。通过防止接地故障升级为电弧闪光事件,还可以提高电气安全性。但是,在电气系统设计期间必须注意确保正确应用了瞬态电压浪涌抑制器(TVSS)和不间断电源(UPS)系统。将专为牢固接地系统设计的TVSS或UPS安装到高电阻接地(HRG)系统中会导致意外故障,从而降低服务连续性。