首页> 外文期刊>Building and Environment >Development and application of a protocol to evaluate impact of duct cleaning on IAQ of office buildings
【24h】

Development and application of a protocol to evaluate impact of duct cleaning on IAQ of office buildings

机译:评估和评估风管清洁对办公楼室内空气质量影响的协议的开发和应用

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

Field investigations reporting increased airborne particles concentrations after ventilation duct cleaning (DC) and emissions of biocides following its use in DC highlight a need to protect building occupants from possible exposures to these harmful pollutants. A new protocol was developed to include tests for assessing duct surface cleanliness and harmful airborne pollutant concentrations associated with DC. Two office buildings undergoing DC were chosen to demonstrate the protocol application. The new protocol was tested for surface cleanliness assessment using a combination of visual inspection and a vacuum test method wherever possible. For airborne pollutant concentration assessments, indoor air exposures to total particle, fungi and VOCs were measured. The test application demonstrates that it is possible to determine harmful airborne pollutant concentration levels attributed to DC activities while still maintaining industrial performance standards of surface cleanliness.
机译:现场调查报告说,通风管道清洁(DC)后空气中的颗粒物浓度增加,在DC中使用后,杀生物剂的排放量增加,这表明需要保护建筑物的居住者免于暴露于这些有害污染物下。制定了新的协议,其中包括用于评估管道表面清洁度和与DC相关的有害空气传播污染物浓度的测试。选择了两个经历DC的办公楼来演示协议的应用。在可能的情况下,结合目视检查和真空测试方法,对新协议进行了表面清洁度评估测试。为了评估空气中的污染物浓度,测量了室内空气中总颗粒,真菌和VOC的暴露量。测试应用表明,有可能确定归因于直流活动的有害空气传播污染物浓度水平,同时仍保持工业标准的表面清洁度。

著录项

  • 来源
    《Building and Environment》 |2012年第10期|p.86-94|共9页
  • 作者单位

    Indoor Environment Research Program, Institute for Research in Construction, National Research Council Canada, Rm 217C, Bldg M-24, 1200 Montreal Road, Ottawa, Ontario, Canada, K1A 0R6;

    Indoor Environment Research Program, Institute for Research in Construction, National Research Council Canada, Rm 217C, Bldg M-24, 1200 Montreal Road, Ottawa, Ontario, Canada, K1A 0R6;

    Indoor Environment Research Program, Institute for Research in Construction, National Research Council Canada, Rm 217C, Bldg M-24, 1200 Montreal Road, Ottawa, Ontario, Canada, K1A 0R6;

  • 收录信息
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    duct cleaning; test protocol; airborne; biocides; particles; surface cleanliness;

    机译:管道清洁;测试协议空降杀菌剂粒子;表面清洁度;