首页> 外文期刊>Automation in construction >Virtual outdoor air flow meter for an existing HVAC system in heating mode
【24h】

Virtual outdoor air flow meter for an existing HVAC system in heating mode

机译:适用于采暖模式下现有HVAC系统的虚拟室外空气流量计

获取原文
获取原文并翻译 | 示例
获取外文期刊封面目录资料

摘要

Measurements from the operation of Heating, Ventilation and Air conditioning (HVAC) system are collected by Building Automation System (BAS) mostly for control purpose. In many air handling units (AHUs) the airflow meter is not installed on the outdoor air stream to reduce the initial costs. To provide such a missing information needed for the ongoing commissioning of HVAC system, a virtual flow meter (VFM) should be implemented in the BAS. This paper presents VFMs for the heating season when the heat recovery coils are used. Two models are presented which predict the outdoor air ratio (factor alpha), in the absence of such an air flow meter, by using BAS trend data. Two energy balance equations, one for the air mixing box and another for the heat recovery coils, are coupled. The results from a case study building show that the two models predict the daily average outdoor air ratio of 0.89 and 0.87, respectively, compared with the reference daily average ratio of 0.86.
机译:楼宇自动化系统(BAS)收集采暖,通风和空调(HVAC)系统运行的测量值,主要用于控制目的。在许多空气处理单元(AHU)中,空气流量计未安装在室外气流上,以降低初始成本。为了提供正在进行的HVAC系统调试所需的此类缺失信息,应在BAS中实现虚拟流量计(VFM)。本文介绍了使用热回收盘管的供暖季节的VFM。提出了两个模型,它们通过使用BAS趋势数据在没有这种空气流量计的情况下预测室外空气比(因子α)。耦合了两个能量平衡方程,一个用于空气混合箱,另一个用于热回收盘管。案例研究大楼的结果表明,与参考日平均比率0.86相比,这两个模型分别预测了日平均室外空气比率为0.89和0.87。