首页> 外文期刊>ASHRAE Transactions >An Analysis of the Effects of Ceiling Height on Air Distribution in Data Centers
【24h】

An Analysis of the Effects of Ceiling Height on Air Distribution in Data Centers

机译:天花板高度对数据中心空气分配的影响分析

获取原文
获取原文并翻译 | 示例
           

摘要

In this study, computational fluid dynamics (CFD) models are used to evaluate how ceiling height affects the overall performance of the air distribution system within a data center environment. First, an underfloor air delivery system is examined while keeping all operational parameters constant and varying only the clear space height. Then, the performance of the same system is evaluated with a dropped ceilingwhile varying the clear space height. Finally, an overhead air distribution system is considered, keeping all operational parameters constant while varying only the clear space height. The performance of each system is evaluated using dimensionless parameters developed previously by others. These indices, supply heat index (SHI) and return heat index (RHI), when used to examine the temperatures at the inlets to the equipment inside the cabinets and at the air handler or computer room air-conditioning unit (CRAC) inlets, provide a measure of how much recirculation and bypass occur within the data space.
机译:在这项研究中,计算流体动力学(CFD)模型用于评估天花板高度如何影响数据中心环境中空气分配系统的整体性能。首先,检查地板下的空气输送系统,同时保持所有运行参数不变,并且仅更改净空高度。然后,在降低净空高度的同时,使用吊顶天花板评估同一系统的性能。最后,考虑使用顶置式空气分配系统,在仅改变净空高度的同时,保持所有操作参数不变。每个系统的性能都使用其他人先前开发的无量纲参数进行评估。这些指数,供热指数(SHI)和回热指数(RHI),当用于检查机柜内部设备的入口以及空气处理器或计算机机房空调单元(CRAC)的入口的温度时,可提供衡量数据空间内发生多少再循环和旁路的指标。