Effect of raised floor height on different arrangement of under-floor air distribution performance in data center

机译:凸起地板高度对数据中心楼层空气分布性能不同布置的影响

获取原文

摘要

In the more and more expanding and complicated data center, requirements on air conditioning system and the air distribution arrangement are getting higher and higher. One of the resolutions is improving the airflow uniformity and cooling the local over-hot area by raising the floor in the data center. With a typical mode of four rows of cabinets in the data center as a sample. This paper uses Computational fluid dynamic (CFD) to investigate the influence of the six raised floor heights (0.2m, 0.4m, 0.6m, 0.8m, lm and 1.2m) on the airflow distribution of three types of under-floor air distribution (the open aisle, the cold aisle containment and the hot aisle containment). Optimization is done on performance indexes, including supply/return heat index (SHI/RHI), return cooling index (RCI) and return temperature index (RTI), with which the condition of subcooling / overheating of all cabinets and the characteristics of the airflow organization in the data center are reflected and the thermal environment in the data center is revealed. Normally, the cooling effect and the uniformity of the airflow can be improved by raising the floor height. However, this won' t work well when the floor height reaches a certain level. Therefore, based on the comparative analysis on the 18 different cases in this investigation, the recommended range of raised floor height in data centers of different construction can be obtained and verified in the experimental tests. The experimental results turn out to be in accordance with the simulation results, which proves the range recommended in this investigation is valuable.
机译:在越来越多的扩展和复杂的数据中心,对空调系统的要求和空气分配装置越来越高。其中一个分辨率通过在数据中心升高地板来改善气流均匀性并冷却局部过热区域。在数据中心中具有四排机柜的典型模式作为样本。本文采用计算流体动力学(CFD)来研究六个凸起地板高度(0.2M,0.4M,0.6M,0.8M,LM和1.2M)对楼层空气分布的气流分布的影响(开放过道,冷过漏箱和热通道遏制)。优化是在性能指标上进行的,包括供应/返回热指数(SHI / RHI),返回冷却指数(RCI)和返回温度指数(RTI),其中所有机柜的过冷/过热的条件和气流的特性数据中心中的组织被反映出来,并揭示了数据中心的热环境。通常,通过升高地板高度,可以提高冷却效果和气流的均匀性。然而,当地板高度达到一定水平时,这赢得了很好的工作。因此,基于对该调查的18个不同案例的比较分析,可以在实验试验中获得和验证不同结构数据中心的推荐楼层高度范围。实验结果符合仿真结果,证明了这项调查推荐的范围是有价值的。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号