A key strategy to increase cooling efficiency that is currently being deployed in operational data centers and discussed by the IT market at large, is to maximize the separation of cold and hot air flow paths. Aisle containment has emerged as a relatively low cost and easy to implement solution. The testing of the Cold Aisle Containment system validated the assumption that utilizing a cold aisle containment system enables the data center environment to support higher density loads while providing a more efficient use of the environmental equipment. Increased efficiencies of up to 40% were achieved utilizing cold aisle containment in comparison to environments without containment. The CRAC units were able to support ΔT's (supply/return) ranging from 75 to 100℉ (23.89 to 37.78℃), depending on load conditions.
机译:当前正在运营数据中心中部署并由IT市场广泛讨论的提高冷却效率的关键策略是最大程度地分离冷热气流路径。过道封闭已成为一种成本相对较低且易于实施的解决方案。冷通道密闭系统的测试验证了以下假设:利用冷通道密闭系统可以使数据中心环境支持更高的密度负载,同时更有效地利用环境设备。与没有安全壳的环境相比,利用冷通道安全壳可以将效率提高多达40%。根据负载条件,CRAC单元能够支持75至100℉(23.89至37.78℃)的ΔT(供应/返回)。