首页> 外文期刊>ASHRAE Transactions >Analysis of Displacement Ventilation for Hospital Patient Rooms
【24h】

Analysis of Displacement Ventilation for Hospital Patient Rooms

机译:医院病房移位通风分析

获取原文
获取原文并翻译 | 示例

摘要

A comparative CFD analysis of overhead supply and displacement ventilation system for a typical hospital patient room indicates that for identical cooling loads the displacement ventilation system can provide relatively better thermal comfort and indoor air quality in the occupied zone. The overhead supply system forms redrculating airflow patterns which cause the airborne particles released from the patient's face to get entrained back into the supply air stream and spread into the entire room. Whereas in the case of displacement system the thermal buoyancy forces create layered stratified temperature distribution causing predominantly horizontal and vertical air flow patterns which keep these particles afloat near the ceiling and create relatively cleaner environment. The analysis of displacement ventilation system further indicates that the supply airflow rate of 4 ACH can create thermal neutral environment in the occupied zone and provide the optimum thermal comfort for the occupants. Also moving the exhaust grille over the patient's head can create least resistive flowpath for airborne pathogens to escape from the room and avoid spread along the ceiling.
机译:对典型医院病房的顶置供气和置换通风系统进行的CFD比较分析表明,对于相同的制冷负荷,置换通风系统可以在占用区域内提供相对较好的热舒适性和室内空气质量。高架供应系统形成重新调节的气流模式,导致从患者面部释放的空气中的颗粒物被带回到供应气流中并扩散到整个房间。而在位移系统的情况下,热浮力会产生分层的分层温度分布,从而形成主要的水平和垂直气流模式,使这些颗粒漂浮在天花板附近并创造相对清洁的环境。置换通风系统的分析进一步表明,4 ACH的送风量可以在居住区创造热中性环境,并为乘员提供最佳的热舒适性。同样,将排气格栅移动到患者头部上方可以为空气传播的病原体从室内逸出并避免沿着天花板扩散创造最小的阻力流路。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号