The low delta-T syndrome exists in many large primary-secondary chilled water systems, which results in the degradation of the system overall energy performance. This paper presents a method and a case study on diagnosing the low delta-T problem resulted from the deficit flow that frequently occurred in the chilled water system of a super high-rise building at its early operation stage. The history operation data during the days when deficit flow and low delta-T syndrome occurred are analyzed. The improper set-point of outlet water temperature on the secondary side of heat exchangers is finally diagnosed as the fault that resulted in the deficit flow and low delta-T syndrome. Diagnosis of this fault was also validated in the in situ experimental tests. The deficit flow could be eliminated if temperature set-point was reset higher. Compared with the original set-point of outlet water temperature on the secondary side of heat exchangers, 87.67 kW (72.37%) of the total power of pumps on primary and secondary sides of heat exchangers could be saved in the test cases when higher set-points were used.
机译:在许多大型的一次-二次冷冻水系统中都存在低delta-T综合症,这导致系统的整体能源性能下降。本文介绍了一种诊断超高层建筑问题的方法和案例研究,该问题是由超高层建筑在其运营早期阶段经常在冷却水系统中出现的流量不足引起的。分析了出现赤字流量和低δ-T综合征期间的历史操作数据。最终,将换热器次级侧出口水温设定值不正确诊断为导致流量不足和低T-T综合症的故障。该故障的诊断也在现场实验测试中得到了验证。如果将温度设定点重新设置得更高,则可以消除流量不足的情况。与更高的设定值相比,与热交换器的二次侧出口水温的原始设定值相比,在测试案例中,热交换器的一次和二次侧泵的总功率可节省87.67 kW(72.37%)。点被使用。

著录项

  • 来源
    《Applied Energy 》 |2012年第2012期| p.597-606| 共10页
  • 作者单位

    Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong;

    Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong;

    Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong;

    Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    chilled water system; low delta-t syndrome; deficit flow; fault diagnosis;

    机译:冷冻水系统;低三角综合征赤字流故障诊断;