首页> 外文期刊>Applied Energy >In-situ implementation and evaluation of an online robust pump speed control strategy for avoiding low delta-T syndrome in complex chilled water systems of high-rise buildings
【24h】

In-situ implementation and evaluation of an online robust pump speed control strategy for avoiding low delta-T syndrome in complex chilled water systems of high-rise buildings

机译:在线高层泵速控制策略的现场实施和评估,该策略可避免高层建筑复杂冷水系统中的低delta-T综合症

获取原文
获取原文并翻译 | 示例
       

摘要

The low delta-T syndrome is one of the major faults that affect the operation and energy performance of the chilled water systems in practice, particularly for the complex chilled water systems. Low delta-T syndrome refers to the situation where the measured mean temperature difference of the overall terminal air-handling units is much lower than the expected normal value. The conventional pump speed control strategies lack the ability to handle the low delta-T syndrome. This paper presents an online robust control strategy for practical applications to avoid the low delta-T syndrome for chilled water systems including complex systems. On top of the conventional control strategies, a temperature set-point reset scheme is developed aiming at providing the reliable temperature set-point for enhancing the operation reliability of chilled water pumps. In addition, a flow-limiting control scheme is employed to perform the function of actively eliminating the deficit flow in the bypass line by a feedback mechanism. This robust pump speed control strategy has been implemented and evaluated on a real complex chilled water system in a high-rise building. The site test results show that the temperature set-point given by the proposed strategy is reliable and the system temperature difference is significantly raised by eliminating the deficit flow problem. When compared to the conventional control strategies, 78% of the total chilled water pump energy was saved in the test period. The actual pump energy saving percentage could be 39% in a year after implementing the robust control strategy in the studied system. (C) 2016 Elsevier Ltd. All rights reserved.
机译:在实践中,低delta-T综合症是影响冷冻水系统运行和能源性能的主要故障之一,特别是对于复杂的冷冻水系统而言。低ΔT综合症是指总的终端空气处理单元的测得平均温度差远低于预期的正常值的情况。传统的泵速控制策略缺乏处理低delta-T综合症的能力。本文提出了一种在线鲁棒控制策略,用于实际应用,可避免对包括复杂系统在内的冷冻水系统使用低delta-T综合症。在常规控制策略的基础上,开发了一种温度设定点重置方案,旨在提供可靠的温度设定点,以增强冷冻水泵的运行可靠性。另外,采用限流控制方案来执行通过反馈机制主动消除旁路管线中的逆流的功能。这种鲁棒的泵速控制策略已在高层建筑中的实际复杂冷冻水系统上实施和评估。现场测试结果表明,所提出的策略给出的温度设定点是可靠的,并且通过消除逆流问题显着提高了系统温差。与常规控制策略相比,在测试期间节省了78%的冷冻水泵总能量。在所研究的系统中实施鲁棒的控制策略后,一年中实际的泵节能百分比可能为39%。 (C)2016 Elsevier Ltd.保留所有权利。

著录项

  • 来源
    《Applied Energy》 |2016年第1期|541-554|共14页
  • 作者单位

    Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hong Kong, Hong Kong, Peoples R China;

    Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hong Kong, Hong Kong, Peoples R China;

    Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hong Kong, Hong Kong, Peoples R China;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Low delta-T syndrome; Chilled water system; Pump speed control; Building energy;