To quantify the performance drop of the air source heat pump (ASHP) system under a special kind of mal-defrost phenomenon appearing in moderate climate conditions, a field test was conducted for 8 days at the initial stage of a heating season in Beijing, China. The mal-defrost was found with the more than 60% frosted area of the outdoor heat exchanger after the system running 5 days. During this frosting period, the system COP was significantly degraded, only 2.3 under an environment temperature of 7.9 ℃. Comparing the test data before and after frosting, it was found that the mal-defrost decreased the COP up to 40.4% and the heating capacity to 43.4%. Such low energy efficiency continued quite a long time until the defrost control was started up manually by the authors. After defrosting, the COP reclaimed to the normal level of 5.0. The origins of this special mal-defrost phenomenon were discussed. And some suggestions were proposed to modify the current defrosting control strategy, which were helpful to avoid the mal-defrost problem in the current ASHP system and therefore improve the system performances.
机译:为了量化在中等气候条件下出现的一种特殊的除霜现象下空气源热泵(ASHP)系统的性能下降,在中国北京一个供暖季节的初期进行了为期8天的现场测试。系统运行5天后,发现室外热交换器结霜面积超过60%时,会出现除霜不良。在此结霜期间,在7.9℃的环境温度下,系统COP显着降低,仅为2.3。比较结霜前后的测试数据,发现除霜效果使COP降低了40.4%,加热能力降低了43.4%。如此低的能源效率持续了很长时间,直到作者手动启动除霜控制。除霜后,COP恢复至正常水平5.0。讨论了这种特殊的除霜现象的起源。并提出了一些修改现有除霜控制策略的建议,有助于避免当前ASHP系统出现除霜问题,从而提高系统性能。

著录项

  • 来源
    《Applied Energy》 |2013年第12期|1138-1145|共8页
  • 作者单位

    Department of Building Environment and Facility Engineering, College of Architecture and Civil Engineering, Beijing University of Technology, No. 100 Pingleyuan, Chaoyang District, Beijing 100124, China;

    Department of Building Environment and Facility Engineering, College of Architecture and Civil Engineering, Beijing University of Technology, No. 100 Pingleyuan, Chaoyang District, Beijing 100124, China;

    Department of Building Environment and Facility Engineering, College of Architecture and Civil Engineering, Beijing University of Technology, No. 100 Pingleyuan, Chaoyang District, Beijing 100124, China;

    Department of Building Environment and Facility Engineering, College of Architecture and Civil Engineering, Beijing University of Technology, No. 100 Pingleyuan, Chaoyang District, Beijing 100124, China;

    Department of Building Environment and Facility Engineering, College of Architecture and Civil Engineering, Beijing University of Technology, No. 100 Pingleyuan, Chaoyang District, Beijing 100124, China;

    Department of Building Environment and Facility Engineering, College of Architecture and Civil Engineering, Beijing University of Technology, No. 100 Pingleyuan, Chaoyang District, Beijing 100124, China;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    Air source heat pump; Mal-defrost; COP; Heating capacity;

    机译:空气源热泵;除霜警察;加热能力;

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号