We have recently commissioned a temporary radiation therapy facility that is novel in two aspects: it was constructed using modular components, and the LINAC was installed in one of the modular sections before it was lifted into position. Additional steel and granular fill was added to the modular sections on‐site during construction. The building will be disassembled and removed when no longer needed. This paper describes the radiation shielding specifications and survey of the facility, as well as the ramifications for acceptance testing occasioned by the novel installation procedure. The LINAC is a Varian 21EX operating at 6 MV and 18 MV. The radiation levels outside the vault satisfied the design criteria, and no anomalous leakage was detected along the joints of the modular structure. At 18 MV and 600 monitor units (MU) per minute, the radiation level outside the primary barrier walls was 8.5μSv/h of photons; there were no detectable neutrons. Outside the direct‐shielded door, the levels were 0.4μSv/h of photons and 3.0μSv/h of neutrons. The isocentricity of the accelerator met the acceptance criteria and was not affected by its preinstallation into an integrated baseframe and subsequent transport to the building site.PACS numbers: 87.52.Df, 87.52.Ga
机译:我们最近已启用了一个临时的放射治疗设施,该设施在两个方面都很新颖:它是使用模块化组件构造的,并且LINAC在提升到位之前已安装在其中一个模块化部分中。在施工过程中,将额外的钢和颗粒填料现场添加到模块部分。不再需要时,将对建筑物进行拆卸和拆除。本文介绍了设备的辐射屏蔽规格和调查,以及新颖的安装程序所引起的验收测试的后果。 LINAC是在6 MV和18 MV下运行的Varian 21EX。保险库外的辐射水平满足设计标准,并且在模块化结构的接缝处未检测到异常泄漏。在每分钟18 MV和600监视单位(MU)的情况下,主要屏障壁外的辐射水平为8.5μSv/ h光子;没有可检测到的中子。在直接屏蔽门外,光子的水平​​为0.4μSv/ h,中子为3.0μSv/ h。加速器的等中心度符合验收标准,并且不受预安装到集成底架中以及随后运输到建筑工地的影响。PACS编号:87.52.Df,87.52.Ga

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号