The controlling algorithm was studied for the inverter-driven multi-type air conditioner using electronic expansion valve(EEV) in outdoor unit. The performance of inverter-driven air conditioner with two different units was investigated by varying the outdoor ambient temperature and compressor speed. Based on the test results, the effect of EEV opening on the indoor unit exit superheat was discussed. For the specified outdoor ambient temperature scope and the EEV opening, the superheats of indoor units decrease with the outdoor ambient temperature rising. Improper distribution of refrigerant into each indoor unit will causes excessive superheat difference between two indoor units. Suggestions were then given for the controlling of the superheat.