The 1/15 reduced-scale experiments using Froude scaling were designed to study the effect on the smoke control efficiency for subway tunnel fires with natural ventilation mode.The propane gas fires with heat release rate 11.48 kW was used,which corresponds to the heat release rate 10 MW in the full-scale tunnel.The temperature distributions under the ceiling were measured by K-type thermocouples to investigate smoke movement,and the velocity of smoke in shafts was measured by hot-wire anemometer to obtain the smoke extract amount of ventilation shafts.The results show that the smoke temperature under the ceiling varies with the longitudinal different distance from fire source.The results also show that the smoke temperature distributions and the smoke control efficiency in tunnel vary with the space between ventilation shafts and vary with the area and the height of ventilation shaft.