The overcurrent (OC) protection limit is set usually accorging to a OC protection setting table on digital integrated protection equipment in mine explode isolation high voltage (HV) vacuum switch. For digital integrated protection equipment, OC protection setting table must be converted to be a microcomputer algorithm. This paper first intro-duced a method of the fitting OC protection setting table to be OC relay inverse time characteristics equations using MATLAB least square fitting. On the basis of analyzing these fitting equations, a notion, “integral limit rate” was put forward initially and a OC in-verse time digital algorithm was developed. MATLAB simulation results and a digital signal processor (DSP) based digital integrated protection equipment running test indicate that this algorithm has less calculation amount, less taking up memory, high control accuracy, implements the no-grade setting of OC delay values, suits for all kinds of low-middle mi-crocomputer system implementation.