首页> 中文期刊> 《消防科学与技术》 >某大型冷库消防安全评估

某大型冷库消防安全评估

         

摘要

The cold storage is a kind of relatively closed building.And the temperature is lower than normal temperature.Thus,cold storage have more particular fire hazards than other building.In this paper,the particular fire hazards were concluded and analysed.The area of the whole cold storage and storage room is beyond the limit of nation standard.Thus,this problem was analysed and discussed.Heat radiation was calculated with formula,as well as software.The fire development process was simulated by FDS.On the other hand,the walking speed in dark was gotten by experiment.The speed is at 0.66 m/s.According to this data,the evacuation time in most unfavorable scenario was calculated.The feasibility of fire protection design and administration in large cold storage was proved scientific and useful.At last,the suggestions on fire protection in large cold storage were put forward.%冷库建筑相对封闭,且建筑内部处于低温环境,具有特殊的火灾危险.针对某大型冷库存在防火分区面积过大等问题,对货架间的热辐射蔓延进行计算,并利用FDS对冷库火灾烟气流动和热辐射蔓延进行模拟分析.开展疏散实验,测得人员在黑暗中行走速度为0.66 m/s,计算冷库中人员的疏散时间.根据火灾蔓延与人员疏散研究结果,论证了在先进的消防技术和有效的消防管理条件下,增大冷藏间占地面积和防火分区面积的可行性.提出了对于大型冷库的消防技术和管理方面的建议.

著录项

相似文献

  • 中文文献
  • 外文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号