首页> 中文期刊>电力自动化设备 >10 kV配电变压器和箱式变电站升压改造至20 kV电压等级的研究

10 kV配电变压器和箱式变电站升压改造至20 kV电压等级的研究

     

摘要

提出具体改造方法,通过计算铁芯参数、高压绕组参数和低压绕组参数,分析了各类型10 kV配电变压器升压改造技术可行性,并比较不同升压改造方案的经济性以确定最优改造方案.分析结果表明:10kV干式变压器具有减容量改造技术可行性,但成本高于直接更换为等容量全新20 kV干式变压器方案,因此宜直接将其更换为20 kV干式变压器;约90%的10 kV油浸式变压器能够顺利等容量升压改造为20 kV油浸式变压器,改造过程中对高压绕组进行更换,其成本约为同容量全新20 kV油浸式变压器价格的35%~45%;欧式箱变具备改造可行性,美式箱变则宜直接更换.%The technical feasibility of voltage upgrading is analyzed by calculating the parameters of core, high-voltage winding and low-voltage winding for various types of 10 kV distribution transformer, and the economic effect is compared among different upgrading schemes for selecting the optimal one. Results show that, 10 kV dry-type transformer can be technically upgraded to 20 kV level by capacity reduction but the cost is higher than new 20 kV dry-type transformer with same capacity, so it should be replaced by 20 kV one;about 90% of 10 kV oil-filled transformers can be easily upgraded to 20 kV level without capacity reduction by high-voltage winding replacement and the cost is about 35 % - 45 % of new 20 kV oil-filled transformer with same capacity;it is possible to upgrade European prefabricated substation from 10 kV to 20 kV; American prefabricated substation should be replaced by 20 kV one.

著录项

相似文献

  • 中文文献
  • 外文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号