Measurement and verification can be successfully used to understand the performance of an energy savings program despite the absence of suitable baseline utility data. The International Performance Measurement and Verification Protocol (IPMVP) includes a method for circumstances where baseline data is unavailable or unreliable. IPMVP Option D is an approach that can supplant missing baseline data through the use of a calibrated computer simulation. A computer model of the energy using systems (typically a building model) can be calibrated to the post-implementation energy use and conditions. The energy improvements are then removed from the simulation to represent the baseline conditions. The resulting energy use is the baseline under an IPMVP Option D method. Savings can be reported simply as the difference between the baseline and post-implementation models, or the savings can be computed with an on-going IPMVP Option C-type approach. The baseline from the model can be used in lieu of the traditionally used pre-project utility bills in order to compare to performance period energy data and compute savings. This article provides additional details about the implementation of IPMVP Option D measurement and verification.
机译:尽管没有合适的基准效用数据,但测量和验证仍可成功用于理解节能计划的性能。国际绩效评估和验证协议(IPMVP)包括一种用于基准数据不可用或不可靠的情况的方法。 IPMVP选项D是一种可以通过使用校准的计算机模拟来替代丢失的基准数据的方法。能源使用系统的计算机模型(通常是建筑模型)可以根据实施后的能源使用和条件进行校准。然后从模拟中删除能量改善值,以表示基准条件。产生的能源使用量是IPMVP选项D方法下的基准。可以将节省量简单地报告为基线模型与实施后模型之间的差异,或者可以使用正在进行的IPMVP Option C型方法来计算节省量。该模型的基线可以代替传统上使用的项目前公用事业账单,以便与绩效期能源数据进行比较并节省计算成本。本文提供了有关IPMVP选项D测量和验证的实施的其他详细信息。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号