A simulation project was conducted for HRSD’s Nansemond WWTP to evaluate the savingspotentials for different aeration control strategies based on ammonia and DO measurements.Special emphasis was put on modeling and analyzing plant constraints including blowerminimum and maximum capacities, diffuser specifications, and mixing requirements.The results show significant savings potential with ammonia- and/or DO-based aeration controlstrategies. Detailed modeling of the air distribution system allowed the design of a controlconcept tailored to the Nansemond plant. Feed-forward ammonia control was only active at lowtemperature (12 ℃) and did not significantly lower effluent ammonia peaks. Therefore feedforwardcontrol was not selected for full-scale implementation as it could not justify additionalinvestment and O&M costs against improved effluent quality or reduced risk.
机译:针对HRSD的Nansemond污水处理厂进行了一个模拟项目,以评估基于氨气和DO的不同曝气控制策略的节省潜力,特别着重于建模和分析工厂约束,包括鼓风机的最小和最大容量,扩散器规格以及混合要求。通过基于氨和/或溶解氧的曝气控制策略显示出巨大的节省潜力。空气分配系统的详细建模允许设计适合Nansemond工厂的控制概念。前馈氨控制仅在低温(12℃)下有效,并没有显着降低流出的氨峰。因此,未选择前馈控制进行全面实施,因为前馈控制无法证明增加废水质量或降低风险的额外投资和运行维护成本是合理的。