Expanding the envelope for indirect/direct evaporative data center cooling using thermal energy storage

机译:使用热能存储扩展范围以进行间接/直接蒸发式数据中心冷却

获取原文
获取原文并翻译 | 示例

摘要

The current philosophy in the design of data center cooling systems matches installed cooling capacity to peak cooling demand at the most challenging ambient condition. This “design point” typically occurs only briefly during hotter months. Cooling capacity remains under-used most of the time. An indirect/direct evaporative cooler with thermal energy storage allow a reduced installed cooling capacity to meet the same need and extends the upper temperature limit. Stored cooling capacity enables load-leveling, or peak-shaving, of cooling demands. Phase change materials present a potential for thermal energy storage to achieve load-leveling at moderate cost. In addition, during days of moderate temperatures thermal energy storage can extend free-cooling capacity when evaporative cooling would otherwise use water. Indirect/direct evaporative coolers that incorporate thermal energy storage can extend the operational envelope beyond current limits and reduce water consumption.
机译:数据中心冷却系统设计中的当前理念将安装的冷却能力与在最具挑战性的环境条件下的峰值冷却需求相匹配。这个“设计点”通常仅在炎热的月份短暂出现。在大多数时候,制冷能力仍未得到充分利用。带有热能存储的间接/直接蒸发式冷却器允许减少安装的冷却量以满足同样的需求,并延长温度上限。存储的冷却能力可实现冷却需求的负载均衡或调峰。相变材料具有潜在的热能存储能力,可以以中等成本实现负载均衡。此外,在温度适中的日子里,当蒸发冷却原本要用水时,热能存储可以扩展自然冷却能力。结合了热能存储的间接/直接蒸发式冷却器可以将运行范围扩展到电流限制之外,并减少水的消耗。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号