首页> 外文会议>Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2012 13th IEEE Intersociety Conference on >Impact of operating conditions on a chiller-less data center test facility with liquid cooled servers
【24h】

Impact of operating conditions on a chiller-less data center test facility with liquid cooled servers

机译:运行条件对采用液冷服务器的无制冷数据中心测试设备的影响

获取原文
获取原文并翻译 | 示例

摘要

Data center cooling can constitute a significant portion of the total data center energy usage, with typical cooling energy expenditures approximately 50% of the IT energy use. Much of this energy consumption occurs at the refrigeration/chiller plant and in the Computer Room Air Handlers (CRAH) that cool and condition the air used to cool the electronics racks. To reduce cooling energy use, a data center test facility was designed and constructed to reduce cooling energy use to less than 5% of the total IT energy use through a combination of warm water cooling of the electronics and liquid-side economization. Several data center operating conditions, such as changes in liquid and air flow rates, heat exchanger arrangements and addition of propylene glycol were investigated to determine their impact on the energy consumption and thermal performance of the key cooling equipment. Day long runs collected from summer and fall days are also reported to illustrate the impact of external weather conditions and loop operating conditions on the thermal performance and energy consumption of the dual-loop data center test facility. The work presented highlights the impact of various operating conditions in influencing the cooling energy use and improving data center energy efficiency in chiller-less, ambient-air cooled data center designs using water cooled servers.
机译:数据中心冷却可能会占数据中心总能耗的很大一部分,典型的冷却能耗约占IT能耗的50%。这种能耗的大部分发生在制冷/制冷机工厂和计算机房空气处理器(CRAH)中,这些处理器对用于冷却电子机架的空气进行冷却和调节。为了减少冷却能源的使用,设计并建造了数据中心测试设施,通过结合电子设备的热水冷却和节省液体的方式,将冷却能源的使用量减少到IT总能源使用量的5%以下。研究了数个数据中心的运行条件,例如液体和空气流速的变化,热交换器的布置以及丙二醇的添加,以确定它们对关键冷却设备的能耗和热性能的影响。还报告了从夏季和秋季收集的全天运行数据,以说明外部天气条件和环路运行条件对双环路数据中心测试设施的热性能和能耗的影响。提出的工作重点介绍了在使用水冷服务器的无冷却器,环境空气冷却的数据中心设计中,各种操作条件对冷却能源使用和提高数据中心能源效率的影响。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号