In this paper, we performed an insulation diagnosis technique for oil-immersed power transformers by an acoustic detection method. Electrode system such as needle to plane electrode was fabricated to simulate a defect of power transformers. In addition, the frequency spectrum of acoustic signals with partial discharge (PD) in insulating oil was analyzed. From the FFT result, the frequency spectrum of the acoustic signals measured by a wide and a narrow band AE sensors were distributed in the range of 50-170 kHz. Therefore, a narrowband AE sensor with a resonant frequency of 140 kHz is suitable for the diagnosis of oil-immersed power transformers. We could find the position of the PD source with an error margin of 10% in the experiments by calculating the position of the PD occurrence using the time difference of arrival measured by five AE sensors.
机译:在本文中,我们通过声学检测方法对油浸电力变压器进行了绝缘诊断技术。制作了电极系统,例如针到平面电极,以模拟电力变压器的缺陷。此外,分析了绝缘油中带有局部放电(PD)的声信号的频谱。根据FFT结果,宽和窄带AE传感器测得的声信号频谱分布在50-170 kHz范围内。因此,谐振频率为140 kHz的窄带AE传感器适用于油浸式电力变压器的诊断。通过使用五个AE传感器测量的到达时间差来计算PD发生的位置,我们可以在实验中找到PD源的位置,误差幅度为10%。