FACTS series devices such as Thyristor Control Series Capacitor (TCSC) are used to improve the power transfer capability of long transmission lines. These series connected FACTS devices inject a series voltage with the line and change the line impedance and cause the impedance seen by distance relay to be lower or higher than the actual line impedance and the distance relay either over reaches or under reaches. In this paper, a new method is proposed to minimize the impact of TCSC on distance relay. In this method each TCSC is equipped with the Variable Impedance Fault Current Limiter, when fault is occurred, this Fault Current Limiter enters in the system and by injecting series impedance, minimizes the impact of TCSC on distance relay. The simulation results verify the suggested method.
机译:FACTS系列设备(如晶闸管控制系列电容器(TCSC))用于提高长输电线路的功率传输能力。这些串联的FACTS器件会向线路注入一个串联电压,并改变线路阻抗,并使距离继电器看到的阻抗低于或高于实际线路阻抗,并且距离继电器超出或低于到达范围。本文提出了一种新的方法来减小TCSC对距离继电器的影响。在这种方法中,每个TCSC都配备了可变阻抗故障电流限制器,当发生故障时,该故障电流限制器会进入系统,并通过注入串联阻抗来最小化TCSC对距离继电器的影响。仿真结果验证了所提方法的有效性。