FACTS series devices such as Thyristor Control Series Capacitor (TCSC) are used to improve the power transfer capability of long transmission lines. These series connected FACTS devices inject a series voltage with the line and change the line impedance and cause the impedance seen by distance relay to be lower or higher than the actual line impedance and the distance relay either, over reaches or under reaches- In this paper, a new method is proposed to minimize the impact of TCSC on distance relay. In this method each TCSC is equipped with the Variable Impedance Fault Current Limiter, when fault is occurred, this Fault Current Limiter enters in the system and by injecting series impedance, minimizes the impact of TCSC on distance relay. The simulation results verify the suggested method.
机译:事实上,诸如晶闸管控制系列电容器(TCSC)的系列装置用于改善长传输线的动力传递能力。这些系列连接的事实器件用线条注入串联电压并改变线路阻抗,并导致距离继电器看到的阻抗低于或高于实际的线路阻抗,即在此纸张中达到或距离中的距离继电器。 ,提出了一种新方法以最大限度地减少TCSC对距离继电器的影响。在该方法中,每个TCSC都配备有可变阻抗故障电流限制器,当发生故障时,该故障电流限制器进入系统中并通过注入串联阻抗,最大限度地减少TCSC对距离继电器的影响。仿真结果验证了建议的方法。