首页> 外文会议>Power quality'99 >Addressing the 'Primary' Problem - Facility Wide Sag Protection
【24h】

Addressing the 'Primary' Problem - Facility Wide Sag Protection

机译:解决“主要”问题-设施范围内的凹陷保护

获取原文
获取原文并翻译 | 示例

摘要

The Orian Rugs, Inc. plant in Anderson, SC utilizes a continuous extrusion process to manufacture yarn for their rug weaving operation. Located at the end of a long distribution feeder, their circuit has been susceptible to frequent power quality disturbances, primarily voltage sags. These disturbances to the sensitive extrusion process are very costly, producing wasted material and lengthy restart times, equating to lost production and lost revenue. Duke Power worked with Orian to increase equipment ride-through capability and decrease sensitivity to power quality disturbances. Using equipment-level solutions, better ride-through performance was attained, however due to the frequency and magnitude of the isturbances from the system, the plant was still experiencing costly disruptions to processes. It was clear that a solution would have to be applied at the system level to achieve the desired performance during disturbances.
机译:位于南卡罗来纳州安德森的Orian Rugs,Inc.工厂利用连续挤压工艺生产地毯,用于地毯织造。它们的电路位于长分布馈线的末端,容易受到频繁的电能质量干扰的影响,主要是电压骤降。这些对敏感的挤出过程的干扰非常昂贵,导致浪费的材料和漫长的重新启动时间,等同于生产损失和收入损失。 Duke Power与Orian合作提高了设备​​穿越能力,并降低了对电能质量干扰的敏感性。使用设备级解决方案可获得更好的穿越性能,但是由于系统干扰的频率和大小,工厂仍在经历昂贵的过程中断。很明显,必须在系统级别应用解决方案才能在干扰期间实现所需的性能。