首页> 外文会议>National Power Systems Conference >Impact of Reactive Current Injection by Islanding Detection Techniques on the Voltage Quality of Distributed Generation
【24h】

Impact of Reactive Current Injection by Islanding Detection Techniques on the Voltage Quality of Distributed Generation

机译:孤岛检测技术注入无功电流对分布式电源电压质量的影响

获取原文

摘要

Many active islanding detection techniques uses current injection through q-axis current controller of grid side converter (GSC) for islanding detection of distributed generation (DG). This paper studies the impact of injection of current on voltage quality of DG. The voltage quality of the DG is investigated by measuring the total harmonic distortion (THD) of voltage at the point of common coupling (PCC). The THD curves are plotted to suggest and help in selecting the amplitude and frequency of q-axis injection current for designing the q-axis injection current based islanding detection technique (IDT). The studies are carried out on a partial converter based small wind energy system on per unit basis to have generalized conclusions. Computer simulations are carried out in MATLAB.
机译:许多主动孤岛检测技术使用通过电网侧转换器(GSC)的q轴电流控制器的电流注入来进行分布式发电(DG)的孤岛检测。本文研究了注入电流对DG电压质量的影响。通过测量公共耦合点(PCC)处电压的总谐波失真(THD)来研究DG的电压质量。绘制THD曲线以建议和帮助选择q轴注入电流的幅度和频率,以设计基于q轴注入电流的孤岛检测技术(IDT)。这些研究是在基于部分变流器的小型风能系统的基础上进行的,具有广义的结论。计算机仿真是在MATLAB中进行的。