首页> 外文期刊>Journal of power electronics >Islanding Detection Method for Inverter-Based Distributed Generation through Injection of Second Order Harmonic Current
【24h】

Islanding Detection Method for Inverter-Based Distributed Generation through Injection of Second Order Harmonic Current

机译:通过注入二阶谐波电流的基于逆变器的分布式发电孤岛检测方法

获取原文
获取原文并翻译 | 示例
           

摘要

This paper proposes a new islanding detection method for inverter-based distributed generators by continuously injecting a negligible amount of 2nd order harmonic current. The proposed method adopts a proportional resonant (PR) controller for the output current control of the inverter, and a PR filter to extract the 2nd order harmonic voltage at the point of common coupling (PCC). The islanding state can be detected by measuring the magnitude ratio of the 2nd order harmonic voltage to the fundamental voltage at the PCC by injecting a 2nd order harmonic current with a 0.8% magnitude. The proposed method provides accurate and fast detection under grid voltage unbalance and load unbalance. The operation of the proposed method has been verified through simulations and experiments with a 5kW hardware set-up, considering the islanding test circuit suggested inUL1741.
机译:通过连续注入微不足道的二阶谐波电流,提出了一种基于逆变器的分布式发电机孤岛检测的新方法。所提出的方法采用比例谐振(PR)控制器来控制逆变器的输出电流,并采用PR滤波器来提取公共耦合点(PCC)的二阶谐波电压。可以通过注入幅度为0.8%的二阶谐波电流来测量PCC处的二阶谐波电压与基波电压的幅度比来检测孤岛状态。所提出的方法在电网电压不平衡和负载不平衡下提供了准确而快速的检测。考虑到UL1741中建议的孤岛测试电路,通过5kW硬件设置的仿真和实验已验证了该方法的操作。