首页> 外文会议>IEEE Workshop on Power Electronics and Power Quality Applications >A Power Quality Case Study of Contact Overhead Lines in the Medellin Metro System
【24h】

A Power Quality Case Study of Contact Overhead Lines in the Medellin Metro System

机译:Medellin Metro System接触桥面线的电能质量案例研究

获取原文

摘要

The Medellin Metro suffered several operation restrictions during the first months of 2018 produced by failures in the contact overhead lines. The common factor of these faults was their location in a mechanical tensor connected through an insulator and a surge arrester to a mast, without having certitude of the specific electrical phenomena behind these events. Thus, this paper presents the results of the studies carried out after the occurrence of the faults, using simulations, historical data and measurements, which identified the combination of several overvoltage phenomena of different origin as the most possible causes. Also, this paper explains the mitigation measures adopted after the contingencies to reduce their future impacts.
机译:Medellin Metro在2018年的第一个月遭遇了几个经营限制,在接触架空线上的故障产生。这些故障的常见因素是它们在通过绝缘体连接的机械张量和桅杆上的机械张力的位置,而不具有这些事件背后的特定电气现象的认证。因此,本文介绍了使用模拟,历史数据和测量发生故障后进行的研究结果,该研究鉴定了不同来源的几种过压现象的组合作为最可能的原因。此外,本文解释了违法行为后采取的缓解措施,以减少其未来的影响。