The internal conductive defects occur when the core rod of the composite insulator is damaged due to moisture. The accurate detection of the defective composite insulator is vital to the safety of the live working on transmission lines. Based on the finite element method, the 3D models 500 kV EHV transmission line composite insulators with the internal conductive defects were built in this paper. The electric field distributions of the different defective composite insulators were calculated, and the influences of the conductive defect length and position on the electric field distribution were also given. The calculation results show that the electric field distribution of the composite insulators with the internal conductive defects will appear obvious distortion. The electric field values at the high voltage end of the insulator and the both ends of the defect will also be increased significantly. These features can be directly applied to the defective composite insulators detection.
机译:当复合绝缘体的芯棒由于水分损坏时,发生内部导电缺陷。精确地检测缺陷复合绝缘体对于在传输线上的现场安全性至关重要。基于有限元方法,在本文中建立了具有内部导电缺陷的3D模型500 kV EHV传输线复合绝缘体。还计算了不同缺陷复合绝缘体的电场分布,还给出了导电缺陷长度和位置对电场分布的影响。计算结果表明,复合绝缘体具有内部导电缺陷的电场分布显得明显失真。绝缘体高压端处的电场值和缺陷的两端也将显着增加。这些特征可以直接应用于缺陷的复合绝缘子检测。