Delayed Current Zero Crossing Characteristics for Circuit Breaker Interrupting Short-Circuit Current Following Permanent Single-phase Ground Fault on Short 1000kV AC Lines

机译:在短1000kV交流管线上延迟断路器中断短路电流的断路器电流零交叉特性

获取原文

摘要

For double or multiple circuits of 1000kV lines on the same tower, where a permanent single-phase ground fault occurs on one circuit, delayed current zero crossing may take place during single-phase reclosing of circuit breaker. This may overburden and even damage the breaker. This paper uses the ATP-EMTP program to simulate various operating conditions of a 1000kV system with varying grid configuration, line length, number of circuits, time of single-phase reclosing and location of fault, and proposes the probability of occurrence of delayed current zero crossing accordingly.
机译:对于在同一塔上的1000kV线的双电路或多个电路,其中在一个电路上发生永久单相接地故障,在断路器的单相重构期间可能发生延迟电流过失。这可能是覆盖层甚至损坏了破坏者。本文采用ATP-EMTP程序模拟了1000kV系统的各种操作条件,具有不同的网格配置,线长度,电路数,单相闭合和故障位置的时间,并提出了延迟电流零的发生概率相应地穿越。