Current zero measurements are performed during short-line fault interruption tests of vacuum circuit breakers. This switching cycle is characterized by a very steep transient recovery voltage. High-resolution measurements of near current-zero arc current and voltage were carried out. Various reignition modes (occurring between 0 and 75 ms after current zero) were observed due to insufficient arcing time or current in excess of the rated short-circuit breaking current. The relationship between post-arc current/charge, reignition mode, and transient recovery voltage is discussed in this paper. In addition to the "classical" post-arc current, already described in the literature, another "late" post-arc current was observed reaching values up to several tens of amperes after severe thermal arcing stress. AH interrupters interrupted at the first or second current zero under the "rated" conditions of short-line fault current and transient recovery voltage.
机译:在真空断路器的短线故障中断测试期间执行电流零测量。该开关周期的特征在于非常陡峭的瞬态恢复电压。进行了接近零电流电弧电流和电压的高分辨率测量。由于电弧放电时间不足或电流超过额定短路分断电流,观察到各种复燃模式(在电流为零后的0至75 ms之间发生)。本文讨论了弧后电流/电荷,复燃模式和瞬态恢复电压之间的关系。除了已在文献中描述的“经典”电弧后电流外,在严重的热电弧应力作用下,还观察到另一种“晚期”电弧后电流达到高达几十安培的值。在短线故障电流和瞬态恢复电压的“额定”条件下,AH灭弧室在第一或第二电流为零时中断。