An algorithm of fault location's detection and resistance's value assessment is described for overhead lines with distributed load in case of isolated neutral. The method is based on the results of measurement of line's mode parameters. A mathematical model is proposed considering the influence of the voltage of the line two wires - rail mode operation-line power automation. Capacitances are placed between each phase line and the ground to increase the accuracy of the method. Accuracy of determining the values of resistance in fault location is analyzed.
机译:故障定位检测和电阻值评估的算法描述于具有分布式中性的分布式负载的架空线。该方法基于线路模式参数的测量结果。建议考虑到线两根轨道模式操作线功率自动化的电压影响的数学模型。电容放置在每个相线和地之间,以提高方法的准确性。分析了确定故障位置中电阻值的准确性。