Development of Predictive Control System Using Just-In-Time Modeling and Enthalpy-Aware Control in Air Conditioners for Large-Scale Data Center

机译:在大规模数据中心空调中使用立即建模和焓感知的预测控制系统的开发

获取原文

摘要

In this research, we propose an energy-efficient predictive control system with outside-air-introduced-type air conditioner in large-scale data center. The system consists of two parts; a predictive part and a control part. We propose to use a dynamic model construction technique called just-in-time (JIT) modeling in the predictive part. It can estimate the air temperature and humidity in the DC room and temperature at the inlet of servers at a high accuracy while the update of data center model is constructed naturally. We also propose to use a control algorithm that utilizes air enthalpy at outside and DC room in addition to the air temperature and humidity in the control part. Owing to the enthalpy, we achieve an effective energy-saving with both wet and dry air. We introduced this predictive control system to a large-scale data center and had verified the improvement in the energy-saving performance for few month. The air temperature and humidity after one hour could be successfully estimated with an accuracy of correlation coefficient of 0.97 or more using the proposed JIT modeling. Furthermore, we demonstrated that the power consumption of the DC room was significantly reduced by 28.9% using the proposed control algorithm compared to that of the conventional control algorithm.
机译:在这项研究中,我们提出了一个节能预测控制系统,在大型数据中心中具有外部空气引入式空调的节能预测控制系统。该系统由两部分组成;预测部分和控制部分。我们建议在预测部分中使用称为即时(JIT)建模的动态模型施工技术。它可以估计直流室内的空气温度和湿度,并且在服务器的入口处,高精度,而是自然地构建数据中心模型的更新。我们还建议使用控制算法,除了控制部中的空气温度和湿度之外,在外部和直流室中使用空气焓。由于焓,我们通过潮湿和干燥空气实现了有效的节能。我们将该预测控制系统介绍到大型数据中心,并验证了节能性能的提高几个月。使用所提出的JIT建模,可以成功地估计一小时后的空气温度和湿度,以0.97或更多的效率为0.97或更高。此外,我们证明,与传统控制算法相比,使用所提出的控制算法,DC室的功耗显着降低了28.9%。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号