摘要

HV line tower footings must be offset from high pressure pipelines to avoid damage due to arcing. A lightning strike to the tower can form both an ionized path to the pipe and flash over a phase insulator. Fault current to the pipe can then cause wall failure. This Phase 1 study proposes parameters for the testing of soil breakdown for impulses, power frequency and power arc sustainment initiated by lightning. An arc model based on electrical input power and thermal dissipation provides physical insight into the breakdown process, helps optimize test parameters and procedures, and will allow interpolation among a limited number of tests.
机译:HV线塔间距必须抵消高压管道,以避免由于电弧引起的损坏。塔架的雷击可以形成管道的电离路径,并在相位绝缘体上闪光。管道的故障电流然后可以导致墙壁故障。本第1阶段研究提出了闪电发起的冲动,功率频率和功率电弧维持的土壤崩溃测试的参数。基于电气输入电源和热耗散的电弧模型提供了对击穿过程的物理洞察力,有助于优化测试参数和程序,并将允许在有限数量的测试中插值。