摘要

HV line tower footings must be offset from high pressure pipelines to avoid damage due to arcing. A lightning strike to the tower can form both an ionized path to the pipe and flash over a phase insulator. Fault current to the pipe can then cause wall failure. This Phase 1 study proposes parameters for the testing of soil breakdown for impulses, power frequency and power arc sustainment initiated by lightning. An arc model based on electrical input power and thermal dissipation provides physical insight into the breakdown process, helps optimize test parameters and procedures, and will allow interpolation among a limited number of tests.
机译:HV线塔基脚必须与高压管道偏移,以免因电弧损坏。塔的雷击既可以形成通往管道的电离路径,又可以闪过相绝缘体。流向管道的故障电流会导致壁故障。这项第一阶段的研究提出了用于测试土壤击穿的参数,这些参数包括雷电引发的脉冲,功率频率和电弧维持性。基于电输入功率和散热的电弧模型可提供对击穿过程的物理洞察力,有助于优化测试参数和过程,并允许在有限数量的测试之间进行插值。