In this paper, the anti-thunder composite insulator combining surge arrester and insulator are developed. The analysis of mechanical performance of the anti-thunder composite insulator is carried out, which shows that the overall mechanical strength needs to be greater than 2.38 kN. A 3D finite model is built up to simulate the behavior of the anti-thunder composite insulator in the distribution line. The simulation results indicate that the stress on the varistor and the core rod decreases with the increase of the size of the core rod. The core rod of 20 mm or more can meet the operation requirements. The simulation indicates that the stress of the varistor determines the force limit of the anti-thunder composite insulator. Therefore, it should pay attention to the performance stability of the varistor of anti-thunder composite insulator under the force.
机译:在本文中,开发了抗雷声避雷器和绝缘体的抗雷晶体绝缘子。进行了抗雷声复合绝缘体的机械性能分析,表明整体机械强度需要大于2.38kn。建立了3D有限型号,模拟了分销线中的抗雷复合绝缘子的行为。模拟结果表明压阻器上的应力随着芯棒的尺寸的增加而降低。芯棒为20 mm或更大,可以满足操作要求。模拟表明压阻器的应力决定了抗雷晶绝缘体的力极限。因此,它应注意在力下反雷复合绝缘子的变阻器的性能稳定性。