首页> 外文会议>IEEE Conference on Energy Internet and Energy System Integration >Study on the Mechanical Performance of Anti-thunder Composite Insulator for Distribution Line
【24h】

Study on the Mechanical Performance of Anti-thunder Composite Insulator for Distribution Line

机译:配电线路防雷复合绝缘子力学性能研究

获取原文

摘要

In this paper, the anti-thunder composite insulator combining surge arrester and insulator are developed. The analysis of mechanical performance of the anti-thunder composite insulator is carried out, which shows that the overall mechanical strength needs to be greater than 2.38 kN. A 3D finite model is built up to simulate the behavior of the anti-thunder composite insulator in the distribution line. The simulation results indicate that the stress on the varistor and the core rod decreases with the increase of the size of the core rod. The core rod of 20 mm or more can meet the operation requirements. The simulation indicates that the stress of the varistor determines the force limit of the anti-thunder composite insulator. Therefore, it should pay attention to the performance stability of the varistor of anti-thunder composite insulator under the force.
机译:本文研制了一种将避雷器和绝缘子相结合的防雷复合绝缘子。对防雷复合绝缘子的力学性能进行了分析,表明整体机械强度需要大于2.38 kN。建立了一个3D有限模型来模拟配电线路中防雷复合绝缘子的行为。仿真结果表明,压敏电阻和芯棒上的应力随着芯棒尺寸的增加而减小。 20 mm或更大的芯棒可以满足操作要求。仿真表明,压敏电阻的应力决定了防雷复合绝缘子的受力极限。因此,在力作用下,应注意抗雷复合绝缘子压敏电阻的性能稳定性。