Study on Autotransformer’s Low Voltage Side Over-current Protection with Circulating Current

机译:具有循环电流的自耦变压器低压侧过电流保护的研究

获取原文

摘要

500kV autotransformer has split type and integrated type. The current transformer (CT) position of low voltage side is different for these two types of autotransformer. This paper analyzes circulating current in autotransformer’s delta winding when single-phase grounding fault takes place on high voltage side. Protection setting method considering circulating current in delta winding is proposed for split type autotransformer. Simulation results verify the position of two types of autotransformer’s CT influences the circulation current in low voltage side protection. Protection setting for an autotransformer used in Shandong electric power grid tests the correctness of the over-current protection setting with circulating current proposed in this paper.
机译:500kv自动转移器具有分割式和集成类型。对于这两种类型的自耦变压器,低电压侧的电流互感器(CT)位置是不同的。本文在高压侧发生单相接地故障时,分析了自动转展形式的循环电流。提出了考虑Δ绕组循环电流的保护设置方法,用于分离式自耦变压器。仿真结果验证了两种类型的自耦变压器CT的位置影响低压侧保护中的循环电流。山东电网用于自耦变压器的保护装置测试过电流保护设置与本文提出的循环电流的正确性。