A new refrigeration facility suitable for experimental investigation of a large variety of cold chain applications has been designed and built from the ground up. The system utilizes a cascade approach and combines two screw compressors in DX configuration cooling ethylene glycol/water (EGW) for low and medium temperature applications. The targeted cooling capacity ranges from 100 kW at -40 °C to 350 kW at 0 °C. Both stages are designed for use with R410A. Unlike systems that are installed in commercial environments, this new facility has been fully instrumented, including test sections with visual access, to obtain accurate performance measurements at different ambient temperatures and load conditions. This paper gives valuable insights and lessons learned from the design and commissioning process including controls, start-up, and oil return issues. Good agreement has been observed between actual and target performance for which the refrigeration facility has been designed.
机译:一种适用于大量冷链应用的实验研究的新型制冷设备已经设计和构建。该系统利用级联方法,将两个螺杆压缩机组合在DX配置冷却乙二醇/水(EGW)中进行低和中温应用。目标冷却能力在-40°C至350kW的范围内为0°C。两个阶段都设计用于R410A。与安装在商业环境中的系统不同,这家新设施已完全仪表,包括具有可视访问的测试部分,以便在不同的环境温度和负载条件下获得精确的性能测量。本文提供了从设计和调试过程中吸取的有价值的见解和经验教训,包括控制,启动和储油问题。在制冷设施的实际和目标性能之间观察到良好的协议。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号