Conversion Factors for Comparing the Performance of Variable Refrigerant Flow Systems

机译:用于比较可变制冷剂流量系统性能的转换因子

获取原文

摘要

Due to the growing concern about energy savings in recent years the Japan Industrial Standards (JIS) committee revised the performance rating of industrial air conditioning systems in October, 2006. The coefficient of performance (COP), the conventional factor, does not consider the actual operation of air conditioning systems corresponding to seasonal temperature changes. Instead it is evaluated under constant temperature conditions. In actual operation, the capacity and power consumption of cooling and heating varies according to outside air temperatures. As a result, the annual performance factor (APF) was adopted as the new criteria to evaluate energy savings performance. Under this method, model cases were designed in order to conduct proper evaluations that are approximately equal to real operation. Factors were estimated by calculations of annual total energy consumption and building thermal load. As the efficiency characteristics of the APF and COP are respectively indicated, calculation of conversion factors became necessary in order to compare their energy saving capabilities. In this study, the energy consumption and its characteristics of the APF and COP machines were calculated using the annual operating data of electric driven heat pumps (EHP) under equivalent load conditions. Effective efficiency was defined as a parameter to estimate conversion factors as follows: Effective efficiency = Annual effective generated heat/Annual energy consumption Using these conversion factors, the performance of machines can be easily compared when evaluation standards change and new air conditioning systems are installed. Furthermore, this approach can also be applied to gas engine driven heat pumps (GHP).
机译:由于近年来,近年来日本工业标准(JIS)委员会越来越多的节能令人担忧于2006年10月修订了工业空调系统的绩效评级。绩效系数(COP),常规因素,不考虑实际对应于季节性温度变化的空调系统的操作。相反,它在恒定温度条件下进行评估。在实际操作中,冷却和加热的容量和功耗根据空气温度而变化。因此,通过年度绩效因数(APF)作为评估能源储蓄绩效的新标准。在这种方法下,设计了模型案例,以进行大约等于实际操作的适当评估。通过计算年度总能耗和建筑热载量来估算因素。随着APF和COP的效率特性分别表示,需要计算转换因子,以便比较它们的节能能力。在该研究中,使用等效负载条件下的电动热泵(EHP)的年度操作数据计算了APF和Cop机器的能耗及其特性。有效的效率被定义为估计转换因子的参数如下:有效效率=使用这些转换因素的年度有效的热/年能耗,可以在评估标准变化和新的空调系统安装新的空调系统时轻松比较机器的性能。此外,这种方法也可以应用于燃气发动机驱动的热泵(GHP)。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号