Field tests on current carrying performances of 1000 kV GIS

机译:现场测试电流携带性能1000 kV GIS

获取原文

摘要

Field tests on 1000 kV (UHV) gas insulated switchgear (GIS) substation equipment have been conducted. This paper presents mainly the results of a temperature rise test which demonstrates the mechanical reliability of the GIS. The specified value of induced current of the enclosure and shunt bars among phases is set as much as 100% of rated normal current. The average temperature of four points defined on GIS enclosure surface is adopted as the base temperature for evaluation of thermal expansion and thermal stress of the enclosure. The limit of temperature rise for the GIS enclosure is as high as 65 K according to the revised specification.
机译:已经进行了1000 kV(UHV)气体绝缘开关设备(GIS)变电站设备的现场测试。本文主要呈现温度升温试验的结果,该试验表明了GIS的机械可靠性。阶段之间的诱导电流的指定值和分流杆的设定为额定正常电流的100%。采用在GIS外壳表面上限定的四个点的平均温度作为基础温度,以评估外壳的热膨胀和热应力。根据修订规范,GIS外壳的温度升高极度高达65 k。