首页> 外文会议>Transmission and Distribution Conference >Power quality evaluation at medical center
【24h】

Power quality evaluation at medical center

机译:医疗中心的电力质量评估

获取原文

摘要

A power quality evaluation was conducted to determine (i) the cause of nuisance tripping of electrical equipment at Baptist Medical Center in Little Rock, Arkansas, and (ii) whether there was any correlation of these nuisance tripping events with voltage sags on the utility system as a result of source-side faults. The facility's total connected load exceeds 6.5 MVA. The interruption of the facility's large chillers and associated air-conditioning equipment, as well as computer and critical diagnostic equipment were of particular concern. This paper describes the different stages of this power quality evaluation which included: (i) an on-site inspection of the facility's electrical system, (ii) continuous power monitoring at the medium-voltage service entrance and at the utilization voltage buses of sensitive electrical equipment in the facility, and (iii) an evaluation of the applicability of a medium-voltage high-speed static source transfer switching system.
机译:进行了电能质量评估,以确定(i)在小岩石,阿肯色州的浸信会医疗中心的电气设备跳闸的原因,以及(ii)这些滋扰跳闸事件与公用事业系统上的电压凹陷是否存在任何相关性由于源侧故障。设施的总连接负载超过6.5 MVA。设施的大型冷水机组和相关空调设备以及计算机和关键诊断设备的中断特别关注。本文介绍了该电能质量评估的不同阶段,包括:(i)设施的电气系统的现场检查,(ii)在中压服务入口处的连续电力监测以及敏感电气的利用电压总线设施中的设备,和(iii)评估中压高速静态源传输切换系统的适用性。