In this paper we tackle the issues of the protection of a synchronous generator field winding in the case of the first ground fault. We analyze the reasons of false operation of the rotor ground fault protection based on the AC injection method on the synchronous machine with a static excitation system. This paper presents the results of the measurements on a ground rotor fault protection of a synchronous generator. These measurements were aimed primarily on harmonic analysis of the field voltage and the current flow through the insulation system of the rotor and also through the rotor ground fault protection during a failure-free steady state of the generator. This submission includes also our results of computer simulations that prove the causes of incorrect operation of the rotor ground fault protection based on the AC method.
机译:在本文中,我们解决了在第一个接地故障的情况下保护同步发电机场绕组的问题。 基于静电激励系统的同步机的AC注射方法,分析转子接地故障保护的假手术的原因。 本文介绍了同步发电机的地面转子故障保护的测量结果。 这些测量主要用于通过转子的绝缘系统和通过转子接地故障保护在发电机的失败稳定状态期间通过转子接地故障保护的谐波分析。 此提交还包括我们基于AC方法的转子接地故障保护操作的计算机模拟结果。